Cecil Hammond The first known installation of a septic tank in the United States was in 1876, although Louis Mouras of Vesoul, France, was given a patent in 1881 and credited with the invention. Baffles, which regulate the flow, were added in 1905 to make the septic tank more efficient. The first baffles were made of oak boards. At the turn of the century, there were some very large community septic tanks. In 1903, four community tanks were constructed in Saratoga, New York, with a total capacity of one million gallons. By 1920, septic tanks began to be a common feature. After World War II, septic tanks became important to housing developments in unsewered areas.
Septic Systems and GroundwaterA few rules of thumb tell us when septic systems are most likely to function properly and minimize groundwater contamination:
Septic Tank Function Sewage or untreated household waste will quickly clog all but the most porous gravel
formations. The septic tank conditions sewage to allow percolation of the liquid portion into the
subsoil. The most important function of septic tanks is to protect the absorption ability of the
subsoil. In doing this the septic tank does the following three things.Removes solids from liquid. As sewage enters the tank, the rate of flow is reduced and heavy solids settle, forming sludge. Grease and other light solids rise to the surface, forming a scum. The sludge and scum are retained and break down while the clarified effluent (liquid) is discharged to the drainfield for soil absorption.
Stores scum and sludge. The solids accumulate in the bottom of the tank to form sludge. The scum is a partially submerged mat of floating solids and grease. Scum and sludge are digested over time and compact-ed into a small volume. Areas with warm climates, such as the southern United States, allow more complete breakdown of solids and scum than in the cooler climates of the North. For this reason, tanks in warm climates do not usually need to be pumped or cleaned out nearly as often as those in cold climates. Regardless of climate, a non-volatile residue of material remains in the tank. Sufficient volume for the solids must be provided in the tank between pumpings or cleanings. If the solids fill the tank and enter the drainfield, the solids can clog the soil in the drainfield. Grease from the kitchen is detrimental to septic tank functions. Effluent from grease traps must go through septic tanks before being discharged to drainfields to prevent soil plugging. The best approach is to put kitchen grease in old milk jugs and place in the garbage rather than into the drain. Small amounts of kitchen grease can go into the septic tank without damaging the system.
Effluent -- Bacteria and NutrientsThe liquid faction that leaves the septic tank and enters the drainfield is called the effluent. The bacterial level of the effluent is quite high, contrary to popular belief. The effluent also contains nitrates (among other nutrients), which move downward. To reduce potential for groundwater contamination by the effluent, many areas restrict building lot sizes. Larger lots reduce loading rates and help protect groundwater. Some areas with porous or sandy soils are located in groundwater recharge areas. These areas may be unsuited for septic tanks or require building lot sizes 50 to 100 percent larger than lots not in the recharge areas. Pathogens break down with soil contact and pathogen levels are reduced as the effluent percolates through the soil. Bacteria eventually die and are removed by the filtering effect of the soil, further purifying the effluent.The drainfield pipe is placed on the contour and perforated to allow the effluent to percolate into the soil. For this reason, the percolation of the soil is a critical factor when determining the amount of drainfield needed. A percolation test of the soil in the drainfield area is essential. If you are considering installing a septic tank, contact your local health department and building inspector for local requirements. The percolation test procedure is described here for your information.
Percolation Test
To conduct a percolation test, dig several straight-sided holes (with a hole digger or auger) at
least 4 inches in diameter down to the drainfield level in the area to be used for the drainfield.
Roughen or scratch any slick clay or compacted soil in the bottom or sides of the holes by
scraping lightly. Remove loose material and add two inches of fine gravel to each hole. Put water
into the holes and saturate the soil, allowing time for clay to swell. All soils except sands must be
soaked at least four hours before percolation test results are analyzed.After soaking, add six inches of water over the gravel and select a fixed point at ground level where repeated measurements can be made. Use the same time interval between measurements and record the settling distance over the time interval. Add water if the depth of the water over the gravel falls below two inches. Take measurements at approximately the same time intervals until a constant rate of percolation is found. The time in minutes required for the water to drop one inch is the percolation rate in minutes per inch (see Table 1). Boring to determine ground water elevation in low areas may be required by the county health department. In such cases, bore to a depth of six feet and provide sufficient time for the water level to stabilize. Sufficient time may mean overnight for clay soils and no less than 30 minutes in sandy soil.
Drainfield SizeOnce the percolation rate is known, the drainfield trench bottom area can be found. Table 1 can be used for residential areas.
Table 1: Residential drainfield area per bedroom in house
If more than 500 linear feet of drainfield is needed, a dosing siphon is required to disperse liquid throughout the drainfield. The siphon must have a capacity equivalent to 60 to 75 percent of the interior volume of the lines to be dosed. A typical cross-section of a drainfield line is shown in Figure 4.
Location and DimensionsDrainfields should be at least 100 feet from the closest well or spring, at least 10 feet from water supply lines, and not closer than 50 feet to a pond or stream.Drainfield trenches should nor-mally be level and not less than 25 inches or more than 36 inches in depth. In rare cases, trenches will be deeper and filled with several feet of gravel to obtain acceptable percolation. The tile drain must have at least 12 inches of soil over the tile. The aggregate should be a minimum of six inches deep under the drain tile. The drainfield trenches should not exceed 36 inches in width.
Septic Tank CapacitySeptic tanks must provide at least 24-hour retention time or at least 750 gallons for a one- or two- bedroom house, 900 gallons for a three-bedroom house and 1,000 gallons for a four-bedroom house. Add 250 gallons for each bedroom exceeding four. Septic tanks must have access openings over inlet and outlet baffles. Access location should be marked and visible for easy inspection.
Selecting A Site
Planning the DrainfieldDrainfields consist of two or more trenches not more than 100 feet in length. Each trench contains sections of open-jointed four-inch drain tile or perforated plastic drain pipe laid with the holes down. The pipe is level to disperse effluent evenly over the soil area. The percolation rate indicates how fast water will penetrate the soil and sizes the drainfield. Some counties require additional soil analysis.
How to Construct Drainfields
![]()
If drainfield trenches are at different elevations, some special requirements should be met. After extending two feet from the box, the water-tight sewers must have a slope of at least l/8-inch per foot down to the individual drainfield trenches. The drainfield lines should also be installed on a uniform grade of not less than two inches nor more than four inches per 100 feet (two inches is preferred). An increased number of shorter trenches is preferable to fewer longer trenches in this situation.
ConclusionsProperly designed and installed septic tanks can function for many years. Annual inspection to determine sludge depth is desirable to prevent tank solids from overflowing and sealing the soil in the drainfield. Minimize the amount of grease from the kitchen and garbage disposal solids going into septic tank. Water conservation reduces the loading and saturation of the drainfield.Check with your local health department for specific requirements in your county before purchasing lots or beginning construction. Septic tanks serving a central system to serve commercial or industrial facilities, institutions, travel trailer and mobile home parks, subdivisions or multiple family dwellings of five or more family units require a design by a professional engineer. To protect groundwater, many areas increase lot size requirements to reduce septic tank densities. Septic tank permits may be subject to additional restrictions in groundwater recharge areas. Contact your local health department or county Extension office for additional information on septic tank maintenance.
Grateful appreciation is expressed to Commissioner Tommy Irvin and the Georgia Department of Agriculture, and to the
U.S. Environmental Protection Agency (Region IV)for financial support of this publication.
The University of Georgia and Ft. Valley State College, the U.S. Department of Agriculture and counties of the state cooperating. The Cooperative Extension Service offers educational programs, assistance and materials to all people without regard to race, color, national origin, age, sex or disability.
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||